Lighting and cooling energy consumption in an open-plan office using solar film coating

被引:65
作者
Li, Danny H. W. [1 ]
Lam, Tony N. T. [1 ]
Wong, S. L. [1 ]
Tsang, Ernest K. W. [1 ]
机构
[1] City Univ Hong Kong, Dept Bldg & Construct, Bldg Energy Res Grp, Kowloon, Hong Kong, Peoples R China
关键词
solar film coating; lighting energy; cooling requirement;
D O I
10.1016/j.energy.2008.03.002
中图分类号
O414.1 [热力学];
学科分类号
摘要
In subtropical Hong Kong, solar heat gain via glazing contributes to a significant proportion of the building envelope cooling load. The principal fenestration design includes eliminating direct sunlight and reducing cooling requirements. Daylighting is an effective approach to allow a flexible building fa ade design strategy, and to enhance an energy-efficient and green building development. This paper studies the lighting and cooling energy performances for a fully air-conditioned open-plan office when solar control films together with daylight-linked lighting controls are being used. Measurements were undertaken at two stages including the electricity expenditures for the office using photoelectric dimming controls only (first stage) and together with the solar control film coatings on the windows (second stage). Electric lighting and cooling energy consumption, transmitted daylight illuminance and solar radiation were systematically recorded and analysed. The measured data were also used for conducting and validating the building energy simulations. The findings showed that the solar film coatings coupled with lighting dimming controls cut down 21.2% electric lighting and 6.9% cooling energy consumption for the open-plan office. (C) 2008 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1288 / 1297
页数:10
相关论文
共 29 条
[21]   Measurements of solar radiation and illuminance on vertical surfaces and daylighting implications [J].
Li, DHW ;
Lam, JC .
RENEWABLE ENERGY, 2000, 20 (04) :389-404
[22]   Daylighting and its implications to overall thermal transfer value (OTTV) determinations [J].
Li, DHW ;
Lam, JC ;
Wong, SL .
ENERGY, 2002, 27 (11) :991-1008
[23]  
Li DHW, 2002, ARCHITECTURAL SCI RE, V45, P21
[24]  
LI DHW, 1999, ARCHITECTURAL SCI RE, V42, P15
[25]  
Littlefair P. J., 2001, Lighting Research and Technology, V33, P43, DOI 10.1177/136578280103300108
[26]   PREDICTING ANNUAL LIGHTING USE IN DAYLIT BUILDINGS [J].
LITTLEFAIR, PJ .
BUILDING AND ENVIRONMENT, 1990, 25 (01) :43-53
[27]   An empirical validation of the daylighting algorithms and associated interactions in building energy simulation programs using various shading devices and windows [J].
Loutzenhiser, Peter G. ;
Maxwell, Gregory M. ;
Manz, Heinrich .
ENERGY, 2007, 32 (10) :1855-1870
[28]  
Roche L., 2000, Light. Res. Technol., V32, P119
[29]   Thin film angular selective glazing [J].
Smith, GB ;
Dligatch, S ;
Sullivan, R ;
Hutchins, MG .
SOLAR ENERGY, 1998, 62 (03) :229-244